
RBHM-xxJNMx & RARL-0xxJE(A)Z w/ Honeywell VisionPro 8000
Common Issues
- Thermostat display blank; no cooling: (Please proceed in order)
- Remove thermostat face from base plate (pull top forward then bottom). Verify no batteries installed. Batteries are not required for operation and are not recommended.
- Batteries installed YES?
- Verify battery terminal clean of corrosion
- If corroded, replace the thermostat with new.
- If not corroded, proceed to 1.b
- Batteries installed NO?
- Re-mount the thermostat. Proceed to 1.b
- Verify circuit breakers are in the ON position
- Locate circuit breaker panel.
- Locate breakers labeled ‘AHU’ (typically 17*19 or 21*23 for GENTRY Homes).
- If breakers are TRIPPED (middle), move to OFF position then ON. IF breaker trips, contact your A/C Tech.
- If breakers are OFF, move to ON position. IF breaker trips, contact your A/C Tech.
- If breakers are ON, proceed to 1.c
- Verify condensate drain is not clogged (EXCLUDES LATITUDES/TUSCANY II - skip to 1.d).
- Locate the attic and access it with a ladder.
- Locate condensate drain trap (Black-insulated ¾” PVC pipe). Remove ¾” PVC cap. With a flashlight, verify if there is a clog.
- If the trap is clogged, proceed to clean with a wet/dry vacuum.
- If the trap does not appear to be clogged, verify by pouring approx. one quart of water into the drain.
- If water overflows, the drain is clogged further down the line and must be cleared.
- Locate black rubber hose under guest bathroom sink.
- With a small bucket and wet/dry vacuum ready, loosen the 5/16” hex screw pipe clamp. Remove black hose by pulling gently yet firmly off the sink drain.
- Clean black hose.
- Remove sink p-trap assembly and clean.
- Re-assemble. Test water flow from upstairs again. If water is still backing up, call your A/C tech.
- If the condensate drain has been cleared and water is flowing normally, proceed to 1.d
- Electrical troubleshooting (if you are unfamiliar with electricity, SKIP this step and call your A/C tech).
- Ensure all circuit breakers (AHU,ACCU), AHU disconnect, ACCU disconnect are all ON.
- Locate thermostat, remove face from base plate.
- Using a multimeter, set to VAC and verify 24VAC between R and C terminals.
- 24VAC YES? Replace the thermostat with a new one.
- 24VAC NO? Proceed to 1.d.2
- Locate AHU. Open panels by removing ¼” hex screws around the perimeter of the cabinet.
- Verify 240VAC across L1&L2 terminals.
- 240VAC YES? Proceed to 1.d.2.b
- 240VAC NO? Check AHU switch integrity. Call your electrician.
- Verify 24VAC at output of transformer.
- 24VAC YES? Proceed to 1.d.2.c
- 24VAC NO? Replace the transformer with a new one.
- Turn off power at AHU switch. Locate and remove the safety float switch. Verify continuity.
- Continuity YES? Proceed to 1.d.2.d
- Continuity NO or SHORT? Replace switch with a new one.
- Turn off power at AHU switch. Verify that there are no shorts.
- If all steps fail, call your A/C tech.
- “There’s water dripping from the pipe from the second floor roof”
- Verify condensate drain is not clogged .
- Locate the attic and access it with a ladder.
- Locate condensate drain trap (Black-insulated ¾” PVC pipe). Remove ¾” PVC cap. With a flashlight, verify if there is a clog.
- If the trap is clogged, proceed to clean with a wet/dry vacuum.
- If the trap does not appear to be clogged, verify by pouring approx. one quart of water into the drain.
- If water overflows, the drain is clogged further down the line and must be cleared.
- Locate black rubber hose under guest bathroom sink.
- With a small bucket and wet/dry vacuum ready, loosen the 5/16” hex screw pipe clamp. Remove black hose by pulling gently yet firmly off the sink drain.
- Clean black hose.
- Remove sink p-trap assembly and clean.
- Re-assemble. Test water flow from upstairs again. If water is still backing up, call your A/C tech.
- If the condensate drain has been cleared and water is flowing normally, but water is still dripping after 12hrs (A/C on), proceed to 2.b
- There may be an insulation issue or crack in the condensate pan. Call your A/C tech.
- “The outdoor unit turns on, but there is no air coming out of the vents.”
- With a ladder or step stool, verify airflow from a supply vent (adjustable louvers).
- Is the airflow WEAK? Check the air filter.
- Is the airflow NON-EXISTENT? There may be an issue with your indoor fan motor. Check article 4 or call your A/C tech.
- “The outdoor unit’s fan spins, but I can’t hear the compressor”
- Reset control board error codes
- Locate circuit breaker panel.
- Locate breakers labeled ‘ACCU’ and ‘AHU’.
- Turn OFF breakers.
- Wait 5-10 min.
- Turn ON breakers.
- If problem persists, there may be an issue with the control board. Call your A/C tech.
- “The outdoor unit doesn’t turn on, but there is air coming out of vents indoor.”
- Verify circuit breakers are in the ON position
- Locate circuit breaker panel.
- Locate breakers labeled ‘ACCU’
- If breakers are TRIPPED (middle), move to OFF position then ON. IF breaker trips, contact your A/C Tech.
- If breakers are OFF, move to ON position. IF breaker trips, contact your A/C Tech.
- If breakers are ON, proceed to 4.b
- Verify ACCU (outdoor unit) disconnect is on
- Locate disconnect switch next to unit outside.
- Verify switch/plug is in the ON position.
- If ON, proceed to 4.c
- If OFF, turn ON.
- If problem persists, proceed to 4.d
- Electrical troubleshooting (if you are unfamiliar with electricity, SKIP this step and call your A/C tech).
- Ensure all circuit breakers (AHU,ACCU), AHU disconnect, ACCU disconnect are all ON.
- Locate outdoor unit. Remove ‘L’ panel. Remove electrical box cover plate.
- Locate LED status display. Refer to legend for code information.
- If ‘0’ or flashing ‘C’ (or ’c’), proceed to 4.c.i.2 (leave panel open)
- If any other codes, call your A/C tech.
- Ensure all circuit breakers (AHU,ACCU), AHU disconnect, ACCU disconnect are all OFF.
- Locate and remove dual capacitor. Verify capacitance with label.
- GOOD? There may be an issue with the control board. Call your A/C tech.
- BAD? Replace the capacitor with a new one.
- There may be an issue with the compressor, control board or outdoor fan motor. Please call your A/C tech.
- “Everything runs, but the house doesn’t get cool or not as cool as before”
- Verify system has been maintained
- Check air filter - replace if dirty
- Check condenser coil is dirty - wash with water if dirty.
- Verify all supply vents are open
- System is low on refrigerant or compressor capacity has been reduced. Call your A/C tech.
*Typically after heavy rain